PIPE SIZE (in.) | Weight (lbs) | w/Water (lbs) | SPAN (ft) | ROD |
3/8″ | 0.7 | 0.8 | 7 | 3/8″-16 |
1/2″ | 1.1 | 1.2 | 7 | 3/8″-16 |
3/4″ | 1.5 | 1.7 | 7 | 3/8″-16 |
1″ | 2.2 | 2.5 | 7 | 3/8″-16 |
11/4″ | 3 | 3.5 | 7 | 3/8″-16 |
11/2″ | 3.6 | 4.3 | 9 | 3/8″-16 |
2″ | 5 | 6.3 | 10 | 3/8″-16 |
21/2″ | 7.6 | 9.4 | 11 | 1/2″-13 |
3″ | 10.2 | 13 | 12 | 1/2″-13 |
31/2″ | 12.5 | 16.3 | 13 | 1/2″-13 |
4″ | 15 | 20 | 14 | 5/8″-11 |
5″ | 20.8 | 28.7 | 16 | 5/8″-11 |
6″ | 28.6 | 39.9 | 17 | 3/4″-10 |
8″ | 43.4 | 63.1 | 19 | 3/4″-10 |
10″ | 64.4 | 95.5 | 22 | 7/8″-9 |
12″ | 88.6 | 132.6 | 23 | 7/8″-9 |
14″ | 107 | 158.2 | 25 | 1″-8 |
16″ | 137 | 206.7 | 27 | 1″-8 |
18″ | 171 | 259.5 | 28 | 1″-8 |
20″ | 209 | 318.4 | 30 | 11/4″-7 |
24″ | 297 | 455.2 | 32 | 11/4″-7 |
- Based on Mss Table 3 & 4
- Based on ASTM A53-86
- * Many codes require pipe hangers to be spaced every 10 ft. regardless of size. Check local codes.
- 1 Cubic Ft. of water weighs 62.41 lbs.
- 1 gallon (U.S.) weighs 8.335 lbs.
- Spacing and capacities are based on water filled pipe. Closer hanger spacing may be required where additional valves and fittings increase the load.