Copper – Internal Working Pressure Type M*

Nominal or standard size, in inches Annealed***
S= 6000 psi 100FS= 5100 psi 150FS= 4900 psi 200FS= 4800 psi 250F
1/4
3/8570485466456
1/2494420403395
5/8
3/4407346332326
1337286275270
1-1/4338287276271
1-1/2331282270265
2299254244239
2-1/2274233224219
3253215207203
3-1/2252214206202
4251213205201
5233198190186
6218186178175
8229195187183
10230195188184
12230195188184

Nominal or standard size, in inches Annealed***
S= 4700 psi 300FS= 4000 psi 350FS= 3000 psi 400F
1/4
3/8447380285
1/2387329247
5/8
3/4319271204
1264225169
1-1/4265225169
1-1/2259221166
2234199149
2-1/2215183137
3199169127
3-1/2197168126
4197167126
5182155116
6171146109
8180153115
10180153115
12180153115

tr>
Nominal or standard size, in inches Drawn**
S= 10,300 psi 100FS= 10,300 psi 150FS= 10,300 psi 200FS= 10,300 psi 250F
1/4
3/8982982982982
1/2850850850850
5/8
3/4701701701701
1580580580580
1-1/4582582582582
1-1/2569569569569
2514514514514
2-1/2471471471471
3435435435435
3-1/2433433433433
4431431431431
5400400400400
6375375375375
8394394394394
10394394394394
12395395395395

Nominal or standard size, in inches Drawn**
S= 10,000 psi 300FS= 9,700 psi 350FS= 9,400 psi 400F
1/4
3/8953925896
1/2825800776
5/8
3/4680660639
1563546529
1-1/4565548531
1-1/2553536520
2499484469
2-1/2457444430
3423410397
3-1/2421408395
4419406394
5388377365
6364353342
8382371359
10383371360
12383372360

* Based on maximum allowable stress in tension (psi) for the indicated temperatures (F).

** When brazing or welding is used to join drawn tube, the corresponding annealed rating must be used.

*** Types M and DWV are not normally available in the annealed temper. Shaded values are provided for guidance when drawn temper tube is brazed or welded. For more information, see Pressure Ratings and Burst Strength.

error: Copy is disabled